RETFLEX-FOC® RV-K 1X300 mm²
Description
Description
Standards
-
ProductIEC 60502; UNE 21123
-
TestIEEE 383
Installation
These cables can be fixed on cable trays, within conduits or fixed to walls. They also can be buried directly with extra mechanical protection.
Core colours
- 2 cores = Brown + Light blue
- 3 cores = Brown + Black + Grey or Light blue + Brown + Green-Yellow
- 4 cores = Black + Grey + Brown + Light blue or Green-Yellow
- 5 cores = Black + Light blue + Brown + Grey + Green-Yellow
- > 5 cores = 1 Green-Yellow + others Black conductors numbered
Marking
Plant nr Nexans RV-K 0.6/1 kV n(G or x) s DD YYYY UNE 21123 AC RETFOC - metric marking.
- n = number of cores
- s = section in mm²
- DD YYYY = traceability
- G = with Green-Yellow
- x = without Green-Yellow
Characteristics
Characteristics
Construction characteristics
Construction characteristics
Conductor flexibility
Flexible class 5
Conductor material
Bare copper
Insulation
XLPE (chemical)
Outer sheath
PVC
Sheath colour
Black
With Green/Yellow core
No
Lead free
Yes
Conductor shape
Circular
With smaller neutral conductor
No
Dimensional characteristics
Dimensional characteristics
Average insulation thickness
- mm
Number of cores
1
Conductor cross-section
300 mm²
Approximate weight
3200 kg/km
Maximum outer diameter
32.5 mm
Neutral conductor section (when smaller)
- mm²
Electrical characteristics
Electrical characteristics
Max. DC resistance of the conductor at 20°C
- Ohm/km
Rated Voltage Uo/U (Um)
0,6/1 kV
Permissible current rating when buried
620 A
Permissible current rating in open air
615 A
Mechanical characteristics
Mechanical characteristics
Cable flexibility
Flexible
Mechanical resistance to impacts
Good
Usage characteristics
Usage characteristics
Chemical resistance
Accidental
Length
- m
Max. conductor temperature in service
90 °C
Operating temperature, range
-10 ... 60 °C
Short-circuit max. conductor temperature
250 °C
Weather resistance
Very good
Flame retardant
EN 50265-2-1
Packaging
Drum
Water proof
Good
Resources
Resources
Documentation
FAMILY EXPORT
xls — 0 B
PEP ECOPASSPORT RV-K
pdf — 4.3 MB
PEP RV-K MONO
pdf — 5.0 MB
PEP RV-K MULTI
pdf — 5.0 MB
Declaration of Performance
- Declaration of Performance n� : 1000232-ESPO
- Certification Date : 10/28/21
- AVCP (Assessment and Verification of Constancy of Performance) : System 3
- Notified body : NB 1722
- Declared performance : Eca
Our websites
Select your country to find our products and solutions
-
Africa
- Africa
- Ghana
- Ivory Coast
- Morocco
- North West Africa
- Americas
- Asia
- Europe
- Oceania